Skip to main content

Conversion: STRING, WSTRING

The operators convert a string (STRING or WSTRING) into the specified target data type and return a type-converted value.

A conversion with a meaningful result is only possible when the operand matches the target data type according to the IEC 61131-3 standard. This is the case if the value of the operand corresponds to a valid constant (literal) of the target data type.

Convertible strings contain:

  • Number with type prefix (example: '16#FFFFFFFF')

  • Number with grouping characters (example: '2#1111_1111')

    Note: The international weight and measure grouping character (thin space) is not accepted. Only the underscore is accepted.

  • Floating-point number, also in exponential notation (example: '9.876' or '1.2E-34')

    Note: Floating-point numbers are not convertible. The comma is treated and truncated as a following character.

  • Time, time of day, and date specification with prefix and size (example: 'T#2h', 'DT#2019-9-9-12:30:30.9')

  • Infinite values (example: '1.7E+400')

  • Additional character after a number (example: '2m' or '3.14')

    These are truncated. Additional characters before a number are not permitted.

  • Spaces before (example: '3.14')

Call syntax: STRING_TO_<target type>(<operand>) , WSTRING_TO_<target type>(<operand>)

Operand

Data Type

Description

Variable or literal

STRING, WSTRING

STRING, WSTRING

Table 13. Casting operators: STRING/WSTRING_TO_<target type>

Operator: STRING

Operator: WSTRING

Example

Return Value

Description

 STRING_TO___UXINT

WSTRING_TO___UXINT

__UXINT, __XINT, __XWORD

 STRING_TO___XINT

WSTRING_TO___XINT

__UXINT, __XINT, __XWORD

 STRING_TO___XWORD

WSTRING_TO___XWORD

__UXINT, __XINT, __XWORD

 STRING_TO_BIT

WSTRING_TO_BIT

BIT

STRING_TO_BOOL

WSTRING_TO_BOOL

STRING_TO_BOOL('TRUE')

STRING_TO_BOOL('true')

WSTRING_TO_BOOL("TRUE")

WSTRING_TO_BOOL("true")

TRUE

BOOL

STRING_TO_BYTE

WSTRING_TO_BYTE

Integer

STRING_TO_DATE

WSTRING_TO_DATE

STRING_TO_DATE('DATE#2019-9-9')

WSTRING_TO_DATE("DATE#2019-9-9")

D#2019-9-9

Syntax: D#yyyy-MM-dd

DATE

STRING_TO_DINT

WSTRING_TO_DINT

If the output data type is larger, then information may be lost.

Integer

STRING_TO_DT

WSTRING_TO_DT

STRING_TO_DT('DT#2019-9-9-1:1:1.1')

WSTRING_TO_DT("DT#2019-9-9-1:1:1.1")

DT#2019-9-9-1:1:1

DT#2019-9-9-1:1:1

Syntax: DT#yyyy-MM-dd-hh:mm:ss

DATE

STRING_TO_DWORD

WSTRING_TO_DWORD

Integer

STRING_TO_INT

WSTRING_TO_INT

STRING_TO_INT('123abc')

WSTRING_TO_INT("123abc")

123

Integer

STRING_TO_LDATE

WSTRING_TO_LDATE

Syntax: LDATE#yyyy-MM-dd

Only the day is displayed.

DATE

STRING_TO_LDT

WSTRING_TO_LDT

Syntax: LDT#yyyy-MM-dd-hh:mm:ss.sss

DATE

STRING_TO_LINT

WSTRING_TO_LINT

Integer

STRING_TO_LREAL

WSTRING_TO_LREAL

STRING_TO_LREAL('1.7E+308')

WSTRING_TO_LREAL("1.7E+308")

1.7000000000000001E+308

REAL, LREAL

STRING_TO_LTIME

WSTRING_TO_LTIME

STRING_TO_LTIME('LTIME#709ms551us615ns')

STRING_TO_LTIME('LTIME#1ms')

WSTRING_TO_LTIME("LTIME#1ms")

LTIME#709ms551us615ns

LTIME#1ms

TIME, LTIME

STRING_TO_LTOD

WSTRING_TO_LTOD

Syntax: LTOD#hh:mm:ss.sssssssss

DATE

STRING_TO_LWORD

WSTRING_TO_LWORD

STRING_TO_LWORD('16#0123456789ABCDEF')

WSTRING_TO_LWORD("16#0123456789ABCDEF")

81985529216486895

Integer

STRING_TO_REAL

WSTRING_TO_REAL

STRING_TO_REAL('1.234')

WSTRING_TO_REAL("1.234")

1.234

When converting from a larger value range, information may be lost or an undefined result may be returned.

REAL, LREAL

STRING_TO_SINT

WSTRING_TO_SINT

Integer

-

WSTRING_TO_STRING

WSTRING_TO_STRING("Hello World!")

Hello World!

STRING_TO_TIME

WSTRING_TO_TIME

STRING_TO_TIME('T#5d4h3m2s')

WSTRING_TO_TIME("T#5d4h3m2s")

T#5d4h3m2s

TIME, LTIME

STRING_TO_TOD

WSTRING_TO_TOD

STRING_TO_TOD('TOD#20:15')

WSTRING_TO_TOD("TOD#20:15")

TOD#20:15:0

DATE

STRING_TO_UDINT

WSTRING_TO_UDINT

Integer

STRING_TO_UINT

WSTRING_TO_UINT

Integer

STRING_TO_ULINT

WSTRING_TO_ULINT

STRING_TO_ULINT('615')

WSTRING_TO_ULINT("615")

615

Integer

STRING_TO_USINT

WSTRING_TO_USINT

Integer

STRING_TO_WORD

WSTRING_TO_WORD

Integer

STRING_TO_WSTRING

-

STRING_TO_WSTRING('Hello World!')

"Hello World!"

WSTRING



Converting to a Boolean value

Operator STRING_TO_BOOL: A value of TRUE is returned only if the operand value is 'TRUE' or 'true'. On the other hand, FALSE is returned for 'True'.

Operator WSTRING_TO_BOOL: A value of TRUE is returned only if the operand value is "TRUE" or "true". On the other hand, FALSE is returned for "True".

_cds_img_fbd_convert_string_to_bool.png
Example 173. FB_ConvertStrings

Declaration

FUNCTION_BLOCK FB_ConvertStrings
VAR_INPUT
END_VAR
VAR_OUTPUT
END_VAR
VAR
	 xReturn_0: BOOL;
	xReturn_1: BOOL;
	dateReturn: DATE;
	dtReturn: DATE_AND_TIME;
	iReturn: INT;
	lrReturn: LREAL;
	lrReturn_0: LREAL;
	lwReturn: LWORD;
	lwReturn_0: LWORD;
	lwReturn_1: LWORD;
	ltReturn: LTIME;
	ltReturn_0: LTIME;
	ltReturn_1: LTIME;
	ltReturn_2: LTIME;
	rReturn: REAL;
	rReturn_0: REAL;
	timReturn: TIME;
	timReturn0: TIME;
	timReturn1: TIME;
	timReturn2: TIME;
	todReturn: TIME_OF_DAY;
	todReturn0: TIME_OF_DAY;
	todReturn1: TIME_OF_DAY;
	todReturn2: TIME_OF_DAY;
	uliReturn: ULINT;
	uliReturn_0: ULINT;
	uliReturn_1: ULINT;
	wReturn: WORD;
	wReturn_0: WORD;
	wReturn_1: WORD;
	wstrReturn: WSTRING;
	wstrReturn_0: WSTRING;
	dtReturn2: DATE_AND_TIME;
END_VAR

Implementation

FUNCTION_BLOCK FB_ConvertStrings
VAR_INPUT
END_VAR
VAR_OUTPUT
END_VAR
VAR
        xReturn_0: BOOL;
        xReturn_1: BOOL;
        dateReturn: DATE;
        dtReturn: DATE_AND_TIME;
        iReturn: INT;
        lrReturn: LREAL;
        lrReturn_0: LREAL;
        lwReturn: LWORD;
        lwReturn_0: LWORD;
        lwReturn_1: LWORD;
        ltReturn: LTIME;
        ltReturn_0: LTIME;
        ltReturn_1: LTIME;
        ltReturn_2: LTIME;
        rReturn: REAL;
        rReturn_0: REAL;
        timReturn: TIME;
        timReturn0: TIME;
        timReturn1: TIME;
        timReturn2: TIME;
        todReturn: TIME_OF_DAY;
        todReturn0: TIME_OF_DAY;
        todReturn1: TIME_OF_DAY;
        todReturn2: TIME_OF_DAY;
        uliReturn: ULINT;
        uliReturn_0: ULINT;
        uliReturn_1: ULINT;
        wReturn: WORD;
        wReturn_0: WORD;
        wReturn_1: WORD;
        wstrReturn: WSTRING;
        wstrReturn_0: WSTRING;
END_VAR
xReturn_0 := STRING_TO_BOOL('FALSE');
xReturn_1 := STRING_TO_BOOL('TRUE');
dateReturn := STRING_TO_DATE('DATE#2019-9-9');
dtReturn := STRING_TO_DT('DT#2019-9-9-1:1:1.1');
iReturn := STRING_TO_INT('123abc');
lrReturn := STRING_TO_LREAL('4.94E-323');
lrReturn_0 := STRING_TO_LREAL('1.7E+308');
lwReturn := STRING_TO_LWORD('16#FFFF_FFFF_FFFF_FFFF');
lwReturn_0 := STRING_TO_LWORD('16#0123456789ABCDEF');
lwReturn_1 := STRING_TO_LWORD('16#0123456789ABCDEF');
ltReturn := STRING_TO_LTIME('LTIME#213503d23h34m33s709ms551us615ns');
ltReturn_0 := STRING_TO_LTIME('LTIME#0ns');
ltReturn_1 := STRING_TO_LTIME('LTIME#1ms');
ltReturn_2 := STRING_TO_LTIME('LTIME#2s');
rReturn := STRING_TO_REAL('6.543e21');
rReturn_0 := STRING_TO_REAL('1.234');
timReturn := STRING_TO_TIME('T#5d4h3m2s');
timReturn0 := STRING_TO_TIME('TIME#1s');
timReturn1 := STRING_TO_TIME('1s');
timReturn2 := STRING_TO_TIME('TIME#5s');
todReturn := STRING_TO_TOD('TOD#12:0:0.1');
todReturn0 := STRING_TO_TOD('TOD#0:0:0.0');
todReturn1 := STRING_TO_TOD('20:15');
todReturn2 := STRING_TO_TOD('TOD#20:15');
uliReturn := STRING_TO_ULINT('18446744073709551615');
uliReturn_0 := STRING_TO_ULINT('1');
uliReturn_1 := STRING_TO_ULINT('0');
wReturn := STRING_TO_WORD('16#FFFF_0000');
wReturn_0 := STRING_TO_WORD('34abc');
wReturn_1 := STRING_TO_WORD('16#34abc');
wstrReturn := STRING_TO_WSTRING('Hello World!');
wstrReturn_0 := STRING_TO_WSTRING('123456789');


Example 174. FB_ConvertWstrings in ST

Declaration

FUNCTION_BLOCK FB_ConvertWstrings
VAR_INPUT
END_VAR
VAR_OUTPUT
END_VAR
VAR
	xReturn_0: BOOL;
	xReturn_1: BOOL;
	dateReturn: DATE;
	dtReturn: DATE_AND_TIME;
	iReturn: INT;
	lrReturn: LREAL;
	lrReturn_0: LREAL;
	lwReturn: LWORD;
	lwReturn_0: LWORD;
	lwReturn_1: LWORD;
	ltReturn: LTIME;
	ltReturn_0: LTIME;
	ltReturn_1: LTIME;
	ltReturn_2: LTIME;
	rReturn: REAL;
	rReturn_0: REAL;
	timReturn: TIME;
	timReturn0: TIME;
	timReturn1: TIME;
	timReturn2: TIME;
	todReturn: TIME_OF_DAY;
	todReturn0: TIME_OF_DAY;
	todReturn1: TIME_OF_DAY;
	todReturn2: TIME_OF_DAY;
	uliReturn: ULINT;
	uliReturn_0: ULINT;
	uliReturn_1: ULINT;
	wReturn: WORD;
	wReturn_0: WORD;
	wReturn_1: WORD;
	wstrReturn: WSTRING;
	wstrReturn_0: WSTRING;
END_VAR

Implementation in ST

FUNCTION_BLOCK FB_ConvertWstrings
VAR
        xReturn_0: BOOL;
        xReturn_1: BOOL;
        dateReturn: DATE;
        dtReturn: DATE_AND_TIME;
        iReturn: INT;
        lrReturn: LREAL;
        lrReturn_0: LREAL;
        lwReturn: LWORD;
        lwReturn_0: LWORD;
        lwReturn_1: LWORD;
        ltReturn: LTIME;
        ltReturn_0: LTIME;
        ltReturn_1: LTIME;
        ltReturn_2: LTIME;
        rReturn: REAL;
        rReturn_0: REAL;
        timReturn: TIME;
        timReturn0: TIME;
        timReturn1: TIME;
        timReturn2: TIME;
        todReturn: TIME_OF_DAY;
        todReturn0: TIME_OF_DAY;
        todReturn1: TIME_OF_DAY;
        todReturn2: TIME_OF_DAY;
        uliReturn: ULINT;
        uliReturn_0: ULINT;
        uliReturn_1: ULINT;
        wReturn: WORD;
        wReturn_0: WORD;
        wReturn_1: WORD;
        wstrReturn: WSTRING;
        wstrReturn_0: WSTRING;
END_VAR

xReturn_0 := WSTRING_TO_BOOL("FALSE");
xReturn_1 := WSTRING_TO_BOOL("TRUE");
dateReturn := WSTRING_TO_DATE("DATE#2019-9-9");
dtReturn := WSTRING_TO_DT("DT#2019-9-9-1:1:1.1");
iReturn := WSTRING_TO_INT("123abc");
lrReturn := WSTRING_TO_LREAL("4.94E-323");
lrReturn_0 := WSTRING_TO_LREAL("1.7E+308");
lwReturn := WSTRING_TO_LWORD("16#FFFF_FFFF_FFFF_FFFF");
lwReturn_0 := WSTRING_TO_LWORD("16#0123456789ABCDEF");
lwReturn_1 := WSTRING_TO_LWORD("16#0123456789ABCDEF");
ltReturn := WSTRING_TO_LTIME("LTIME#213503d23h34m33s709ms551us615ns");
ltReturn_0 := WSTRING_TO_LTIME("LTIME#0ns");
ltReturn_1 := WSTRING_TO_LTIME("LTIME#1ms");
ltReturn_2 := WSTRING_TO_LTIME("LTIME#2s");
rReturn := WSTRING_TO_REAL("6.543e21");
rReturn_0 := WSTRING_TO_REAL("1.234");
timReturn := WSTRING_TO_TIME("T#5d4h3m2s");
timReturn0 := WSTRING_TO_TIME("TIME#1s");
timReturn1 := WSTRING_TO_TIME("1s");
timReturn2 := WSTRING_TO_TIME("TIME#5s");
todReturn := WSTRING_TO_TOD("TOD#12:0:0.1");
todReturn0 := WSTRING_TO_TOD("TOD#0:0:0.0");
todReturn1 := WSTRING_TO_TOD("20:15");
todReturn2 := WSTRING_TO_TOD("TOD#20:15");
uliReturn := WSTRING_TO_ULINT("18446744073709551615");
uliReturn_0 := WSTRING_TO_ULINT("1");
uliReturn_1 := WSTRING_TO_ULINT("0");
wReturn := WSTRING_TO_WORD("16#FFFF_0000");
wReturn_0 := WSTRING_TO_WORD("34abc");
wReturn_1 := WSTRING_TO_WORD("16#34abc");


Example 175. FBD implementation language
_cds_img_fbd_convert_string.png